A water-side economizer is a cooling system arrangement that uses favorable outdoor conditions to reduce or eliminate the need for mechanical refrigeration.
In a conventional chilled-water data center, a water-side economizer commonly uses a cooling tower and a liquid-to-liquid heat exchanger to cool the chilled-water circuit without relying entirely on the chiller compressor.
When outdoor conditions are sufficiently favorable, the economizer may provide the required cooling duty. Under intermediate conditions, it may precool returning water while a chiller supplies the remaining cooling.
However, free cooling does not mean zero electricity consumption. Cooling tower fans, pumps, controls, and other auxiliary equipment still require power.
For data center engineers and equipment buyers, the important questions are when water-side economizing is technically feasible, how much mechanical cooling it can replace, and what equipment and operating data are needed to evaluate the complete system.
A water-side economizer (WSE), sometimes called a waterside or fluid economizer, uses an external heat rejection source to cool a circulating liquid when environmental conditions permit.
Rather than transferring all the cooling load through a vapor-compression refrigeration cycle, the system uses the available temperature difference between the facility cooling water and the heat rejection circuit.
In a common water-cooled chiller plant, a cooling tower rejects heat from the condenser-water circuit to outdoor air through evaporative cooling.
When the outdoor wet-bulb temperature is sufficiently low, the tower can produce cooling water suitable for use by an economizer heat exchanger.
A simplified heat rejection path is:
Data Center Cooling Load → Chilled-Water Return → Economizer Heat Exchanger → Cooling Tower Circuit → Outdoor Air
The heat exchanger transfers heat from the building's chilled-water circuit into the tower-water circuit without intentionally mixing the fluids.
A conventional chiller uses a refrigeration compressor and associated components to remove heat from the chilled-water circuit.
A water-side economizer uses a liquid-to-liquid heat exchanger and available heat rejection capacity to reduce the required compressor operation.
The economizer does not create cooling independently of outdoor conditions.
Its available capacity depends on water temperatures, flow rates, equipment performance, and environmental conditions.
No.
An air-side economizer uses favorable outdoor air conditions to reduce mechanical cooling of the data center air.
A water-side economizer transfers heat through a liquid circuit and associated heat rejection equipment.
This distinction is important because the water-side arrangement can reduce the need to introduce large quantities of outdoor air directly into the IT environment.
The heat rejection equipment removes heat from the circulating liquid.
In a conventional cooling tower economizer, evaporative cooling allows the tower's leaving-water temperature to approach the outdoor wet-bulb temperature.
Actual performance depends on tower design, airflow, water flow, heat load, and ambient conditions.
Some broader fluid-economizer architectures use dry coolers or closed-circuit fluid coolers. These operate under different physical limitations and should not be assumed equivalent to a conventional open cooling tower arrangement.
A plate heat exchanger is commonly installed between the tower-water circuit and the chilled-water circuit.
Its functions include:
Transferring heat between the separate liquid circuits
Limiting routine exposure of the closed chilled-water system to tower-water contaminants
Accommodating appropriate differences in fluid chemistry
Providing a defined thermal separation boundary
The exchanger must be selected for the required heat-transfer duty, operating temperatures, pressure limits, and allowable pressure drops.
Gasketed plate-and-frame heat exchangers are commonly considered for larger serviceable installations, but the appropriate construction depends on the application.
A water-side economizer requires more than a heat exchanger.
Depending on the design, its supporting equipment may include:
Cooling tower and chilled-water pumps
Isolation and bypass valves
Temperature and pressure sensors
Flow measurement and control devices
Strainers or filtration equipment
Heat exchanger protection and maintenance provisions
Building management system (BMS) interfaces
The piping and control arrangement determines whether economizer and mechanical cooling can operate separately or together.
A Coolant Distribution Unit (CDU) commonly separates a data center's Facility Water System (FWS) from its Technology Cooling System (TCS).
A water-side economizer is usually part of the facility cooling or heat rejection architecture.
The economizer reduces mechanical cooling demand, while the CDU manages the interface with liquid-cooled IT equipment.
These two functions may exist in the same data center, but they should not be confused.
For further background, see Why Data Centers Separate Facility and IT Cooling Loops.
A well-designed economizer system may operate in different modes depending on outdoor conditions and cooling demand.
Full economizer operation occurs when the external cooling source and heat exchanger can meet the required chilled-water duty without mechanical refrigeration.
Under these conditions, the chiller compressor may be shut down or bypassed according to the approved system design.
The cooling tower, pumps, and controls may continue operating.
Full economizer capability must be verified at the required supply temperature, flow rate, and heat load.
During intermediate outdoor conditions, the economizer may not be able to reach the required chilled-water supply temperature independently.
However, it may still reduce the temperature of the water returning from the data center.
A chiller then supplies the remaining cooling.
This arrangement can reduce mechanical refrigeration duty when properly designed and controlled.
When the available external cooling conditions do not provide useful economizer capacity, the system may operate primarily through the chiller.
The economizer can be bypassed or isolated according to the hydraulic arrangement.
The transition must preserve required chilled-water flow, temperature stability, and equipment safety.
An integrated economizer can operate simultaneously with mechanical cooling.
A common integrated arrangement positions the economizer heat exchanger upstream of the chiller so that the water can be precooled before entering the chiller.
A non-integrated arrangement generally uses either the economizer or the chiller to supply the cooling load rather than operating both simultaneously.
Integrated operation can utilize available economizer capacity even when outdoor conditions are not sufficient for full compressor-free cooling.
However, the actual benefit depends on system design, hydraulic configuration, and controls.
Before selecting equipment, request a written sequence explaining:
Conditions for starting economizer operation
Conditions for full and partial economizer modes
Chiller enable and disable logic
Valve and pump changeover requirements
Minimum flow and temperature restrictions
Failure and alarm response
The commissioning plan should confirm that the system maintains the required cooling conditions while changing between full economizer, partial economizer, and mechanical cooling modes.
Control behavior must be verified under the applicable operating conditions rather than inferred from a conceptual diagram.
For conventional cooling tower economizers, outdoor wet-bulb temperature is a major factor.
Evaporative cooling performance depends on the difference between the tower water temperature and the air's wet-bulb temperature.
The tower cannot be assumed to deliver water at the outdoor wet-bulb temperature itself.
A finite temperature approach is required.
Cooling tower approach can be expressed as:
Cooling Tower Approach = Tower Leaving-Water Temperature − Outdoor Wet-Bulb Temperature
The approach depends on cooling tower design and the actual operating conditions.
A smaller approach generally requires greater heat rejection capability or different operating conditions.
The economizer heat exchanger also requires a temperature difference.
For a typical counterflow arrangement, a cold-end approach can be defined as:
Heat Exchanger Cold-End Approach = Chilled-Water Leaving Temperature − Tower-Water Entering Temperature
This temperature difference influences the minimum chilled-water temperature achievable at the specified operating point.
The heat exchanger selection must also satisfy the required capacity and pressure-drop limits.
The system's required chilled-water temperature strongly affects economizer availability.
If the facility can operate with warmer chilled water, the economizer may provide useful cooling during a wider range of outdoor conditions.
However, the permitted water temperature depends on the data center's air cooling equipment, liquid cooling equipment, and applicable IT thermal requirements.
A single winter design point cannot establish annual economizer performance.
Engineers should evaluate hourly or suitably representative weather data together with the expected cooling load and equipment performance.
The number of full and partial economizer hours depends on the specific site and cooling architecture.
The following example explains the temperature relationships. It does not represent Aidear equipment ratings or actual data center operating results.
Assume the following design requirements:
Parameter | Illustrative Value |
|---|---|
Required chilled-water supply | 16°C |
Chilled-water return | 24°C |
Cooling tower approach | 4 K |
Economizer heat exchanger cold-end approach | 3 K |
Outdoor wet-bulb temperature, Case A | 7°C |
Outdoor wet-bulb temperature, Case B | 14°C |
These approach values are assumptions for illustrating the calculation. Their achievement at the required duty must be confirmed by equipment selection.
First estimate the tower leaving-water temperature:
Tower Leaving Water = Wet-Bulb Temperature + Tower Approach
Tower Leaving Water = 7 + 4 = 11°C
The illustrative minimum chilled-water leaving temperature based on the assumed cold-end approach is:
11 + 3 = 14°C
Because this is below the required 16°C supply temperature, full economizer operation may be feasible.
Actual full-load capability still depends on heat exchanger performance, flow rates, tower capacity, the hot-end temperature difference, and controls.
At an outdoor wet-bulb temperature of 14°C:
Tower Leaving Water = 14 + 4 = 18°C
The illustrative cold-end temperature becomes:
18 + 3 = 21°C
This is warmer than the required 16°C supply temperature.
The economizer cannot independently achieve the specified supply temperature under the assumed conditions.
However, it may be able to precool the 24°C returning water, allowing the chiller to provide the remaining cooling.
The actual precooling duty must be calculated rather than assumed.
The temperature calculations establish preliminary feasibility, not a guaranteed equipment selection.
A detailed evaluation requires:
Cooling load
Water or glycol properties
Flow rates on both sides
Cooling tower performance
Heat exchanger thermal selection
Pressure losses
Chiller performance
Control requirements
Illustrative Example: The temperatures and approach values are hypothetical and are not manufacturer test results or universal design recommendations.
A water-side economizer can reduce compressor operating hours or mechanical cooling duty when outdoor conditions permit.
However, the energy benefit must be calculated for the actual system.
In full economizer mode, the chiller compressor may not be required to meet the cooling load.
In partial mode, the chiller may operate at a reduced cooling duty.
The corresponding electrical savings depend on the chiller's part-load performance and operating conditions.
Economizer operation may require cooling tower fan power, circulating pump power, and auxiliary electrical input.
Therefore:
Net Energy Savings = Avoided Mechanical Cooling Energy − Additional Economizer-Related Energy
The calculation must use consistent system boundaries and account for equipment that operates in both cases.
Cooling tower economizers commonly rely on evaporative cooling.
Their operating water demand includes evaporation and other losses associated with the tower's water management system.
Water treatment, blowdown, scaling, biological control, and maintenance must be evaluated.
Energy savings do not automatically mean reduced water consumption.
In addition to energy consumption, the economic analysis should consider installation costs, heat exchanger maintenance, pumping requirements, water treatment, redundancy, and equipment service life.
No universal payback period or energy-saving percentage should be applied without project-specific evidence.
A conventional cooling tower economizer and a dry cooler-based free-cooling system can both reduce compressor dependence, but their performance is governed by different environmental conditions.
Selection Factor | Cooling Tower Water-Side Economizer | Conventional Dry Cooler Free Cooling |
|---|---|---|
Heat rejection method | Evaporative cooling | Sensible heat transfer to air |
Main ambient reference | Outdoor wet-bulb temperature | Outdoor dry-bulb temperature |
Normal evaporative water use | Yes | No, for conventional dry operation |
Fluid arrangement | Tower water often separated by a heat exchanger | Closed liquid circuit, with additional separation where needed |
Main constraints | Tower approach, water quality, exchanger approach | Dry cooler approach, air temperature, airflow |
Maintenance focus | Tower water treatment, fouling, pumps, fans | Coils, fans, fluid protection, pumps |
Free-cooling capability | Depends on site wet-bulb conditions and equipment | Depends on site dry-bulb conditions and equipment |
Neither option is universally superior.
Water availability, facility temperature requirements, local climate, maintenance capacity, and energy costs influence the preferred solution.
For equipment-specific performance assessment, see Aidear's Dry Cooler Performance Verification Guide.
Modern data centers may combine liquid-cooled servers with traditional air cooling systems.
These systems do not necessarily require the same cooling-water temperatures.
Where IT equipment and CDU specifications permit warmer facility water, the available temperature difference to outdoor conditions may increase.
This can extend the operating range of some economizer arrangements.
However, the actual limits must be confirmed against the IT equipment's coolant temperature, flow, and reliability requirements.
A liquid-to-liquid CDU commonly transfers heat from the Technology Cooling System to the Facility Water System.
Its required approach temperature must be included in the full temperature schedule.
If another economizer heat exchanger separates the facility system from an outdoor cooling circuit, there may be multiple heat-transfer boundaries.
A facility may use separate water temperature levels for direct liquid cooling and air cooling.
The cooling plant architecture must account for the requirements of all loads and the interaction between their control systems.
Before requesting equipment quotations, establish the design basis for the complete system.
RFQ Item | Information to Confirm |
|---|---|
Application | Data center chilled-water plant or facility liquid cooling |
Cooling duty | Normal, peak, and minimum operating loads |
Required supply temperature | Chilled-water or FWS supply requirement |
Return temperature | Expected return conditions |
Site climate | Annual wet-bulb and dry-bulb weather data |
Heat rejection equipment | Cooling tower, closed-circuit cooler, or dry cooler |
Cooling fluids | Water chemistry, glycol type, concentration |
Flow rates | Both sides of the economizer heat exchanger |
Exchanger approach | Required at the specified duty |
Pressure drop | Maximum permitted on each circuit |
Operating modes | Full economizer, partial economizer, mechanical cooling |
Controls | Temperature reset, sequencing, valves, pumps, alarms |
Reliability | Redundancy, isolation, bypass, failure response |
Maintenance | Filtration, water treatment, cleaning, access |
Documentation | Thermal selection, P&ID, control sequence, testing requirements |
For the plate heat exchanger, request:
Required and calculated heat-transfer duty
Four terminal temperatures
Fluid composition and properties
Both flow rates
Allowable pressure drops
Plate and gasket or brazing material specifications
Design pressure and temperature
Fouling assumptions and maintenance provisions
Connection details and overall dimensions
Applicable inspection and testing documentation
A nominal kW capacity alone is not enough to verify suitability.
The system designer should provide a complete operating concept showing where the economizer connects to the chilled-water plant, how the chiller is bypassed or operated in series, and how cooling continuity is maintained during mode changes.
Not necessarily.
It may eliminate compressor operation during favorable outdoor conditions, but a chiller or other supplemental cooling source may still be required.
No.
Cooling tower fans, pumps, valves, and controls still require energy.
The benefit comes from reducing mechanical refrigeration energy relative to the alternative operating mode.
A separate plate heat exchanger is common in conventional open cooling tower economizer arrangements.
Other approved heat rejection and fluid-cooling configurations may use different forms of heat exchange or integrated equipment.
No.
Suitability depends on site weather, required water temperature, heat load, and equipment performance.
Annual operating-hour analysis is necessary.
Yes, if the facility cooling architecture and temperature conditions are compatible.
The economizer and CDU perform different functions and must be evaluated as parts of the overall system.
A water-side economizer uses favorable outdoor conditions to reduce the mechanical cooling required by a data center.
In conventional chilled-water systems, cooling towers and liquid-to-liquid heat exchangers commonly provide this function.
Full economizer operation may allow the chiller compressor to stop, while an integrated system can provide partial cooling when mechanical refrigeration is still necessary.
The actual benefit depends on outdoor conditions, required supply temperature, heat exchanger approach, flow rates, pumping and fan energy, and controls.
For engineering and procurement teams, the correct approach is to evaluate the complete cooling architecture and its operating conditions rather than selecting individual equipment only by nominal capacity.
Aidear provides plate heat exchanger products and dry cooler products for relevant industrial and facility cooling applications.
If your data center project involves an economizer heat exchanger, outdoor fluid cooling equipment, or a facility-side thermal separation requirement, provide the cooling duty, fluids, temperatures, flow rates, allowable pressure drops, and installation conditions.
Equipment compatibility, performance, and project-specific technical requirements must be confirmed during selection.
Request a Custom Quote to discuss your cooling equipment requirements.
How Supply Water Temperature Changes Data Center Cooling Efficiency
Where Should a Plate Heat Exchanger Be Installed in a Data Center Cooling Loop?
Microchannel Condenser Selection for R290 Industrial Chillers: What OEM Buyers Should Verify
Dry Cooler vs Air-Cooled Chiller for Data Center Liquid Cooling: How to Choose
Custom Fin-and-Tube Coil RFQ Guide for Industrial Refrigeration OEMs
Why Data Center Cooling Systems Use Separate Facility and IT Water Loops
What Causes Thermal Stress in Shell-and-Tube Heat Exchangers?
Microchannel vs Fin-Tube Heat Exchangers: Key Differences Explained