You are here: Home » Blog » Where Should a Plate Heat Exchanger Be Installed in a Data Center Cooling Loop?

Where Should a Plate Heat Exchanger Be Installed in a Data Center Cooling Loop?

Views: 80     Author: Site Editor     Publish Time: 2026-11-20      Origin: Site

facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
sharethis sharing button

In a liquid-cooled data center, a plate heat exchanger is often used to transfer heat between two circulating fluid systems without intentionally mixing their coolants. However, its installation location depends on the cooling architecture and the purpose of the separation boundary.

A plate heat exchanger may be installed inside a Coolant Distribution Unit (CDU), between an outdoor dry cooler circuit and an indoor facility water loop, or at another engineered interface in the heat rejection system.

These locations serve different functions. A CDU heat exchanger primarily separates facility cooling water from the coolant circulating through IT equipment. A facility-side intermediate heat exchanger may separate glycol, cooling tower water, or another external cooling source from an internal circuit.

Choosing the correct position requires an understanding of heat flow, coolant quality, temperature approach, pressure drop, maintenance access, and system availability.

This guide explains the main installation positions and what data center engineers and equipment buyers should verify before approving a plate heat exchanger arrangement.

1. Understand the Cooling Loops Before Choosing a Location

1.1 Facility Water System (FWS)

Facility water systems utilize a building's existing cooling infrastructure to provide cooling capacity.

Depending on the installation, it can be connected to chillers, dry coolers, cooling towers, or other heat dissipation equipment.

Facility water systems transfer heat from ambient temperature and pressure units (CDUs) or other cooling equipment to the facility's heat dissipation system.

1.2 Technology Cooling System (TCS)

The Technology Cooling System circulates coolant through liquid-cooled IT equipment.

A typical direct-to-chip TCS includes:

  • Server cold plates

  • Rack or row manifolds

  • Coolant piping and hoses

  • Quick-disconnect fittings

  • Monitoring and filtration components

  • Circulation equipment associated with the CDU

Coolant returning from the IT equipment carries the absorbed heat toward the CDU.

1.3 The Heat Exchanger Creates a Thermal Boundary

In a conventional liquid-to-liquid CDU, the plate heat exchanger transfers heat from the TCS to the FWS while maintaining separate fluid passages.

A simplified heat-transfer path is:

Server Cold Plates → TCS Return → CDU Heat Exchanger → FWS Return → Facility Cooling Plant

The cooled TCS fluid returns to the servers, while the warmer FWS fluid returns to the facility plant.

For an explanation of the two circuits, see Why Data Centers Separate Facility and IT Cooling Loops.

2. Location One: Inside the CDU Between FWS and TCS

For many systems that directly liquid cool the chip, the motherboard heat exchanger is located inside the cooling unit (CDU).

This is one of the most common solutions for establishing a controlled interface between facility cooling infrastructure and liquid-cooled IT equipment.

2.1 How the Connections Work

The plate heat exchanger has separate flow paths.

On the facility side:

FWS Supply → Heat Exchanger → FWS Return

On the technology side:

TCS Return → Heat Exchanger → TCS Supply

The FWS supplies the cooling potential, while the TCS carries heat from the IT equipment.

The two circuits do not intentionally exchange fluid during normal operation.

2.2 In-Rack, In-Row, or Floor-Standing CDU Placement

The physical CDU location may vary.

In-rack CDU: Installed within a server rack or associated rack arrangement, subject to available space and the equipment manufacturer's design.

In-row CDU: Positioned near a group of racks, allowing distribution to multiple IT cooling connections.

Floor-standing or centralized CDU: Located in a designated equipment area and connected to a wider liquid cooling distribution network.

The heat exchanger is typically integrated into the CDU package, but its exact internal mounting position and piping sequence are manufacturer-specific.

There is no universal requirement to mount the heat exchanger at one fixed distance from the racks.

2.3 Why CDU Placement Affects System Design

The distance between the Cooling Distribution Unit (CDU) and IT equipment impacts the entire hydraulic network.

Longer piping paths result in greater pressure losses, additional coolant usage, and more potential connection points.

However, installing the CDU close to the servers is not always optimal.

Designers must also evaluate factors such as ease of maintenance, floor load, electrical interfaces, leak detection, redundancy, and service isolation.

2.4 How Pumps and Filters Relate to the Heat Exchanger

A CDU may include TCS pumps, filters, valves, sensors, expansion provisions, and other hydraulic components.

Their actual arrangement depends on the CDU design.

2.4.1 Filtration Before Sensitive Flow Passages

Filters or screens can be used to protect heat exchangers and IT cooling equipment from particulate contamination.

The location and rating of the filter must comply with the approved CDU design and water quality requirements.

Before adding a filter, its pressure drop, maintenance requirements, and impact on available flow rate must be checked.

Installation Check: Confirm the Hydraulic Schematic

Before approving the CDU arrangement, request a piping and instrumentation diagram (P&ID) showing:

  • Four heat exchanger ports and flow directions

  • FWS and TCS supply and return connections

  • Pump locations

  • Filters and strainers

  • Temperature and pressure measurement points

  • Isolation, venting, and drainage provisions

  • Applicable bypass and control valves

  • Required protective devices

The approved manufacturer schematic should determine the final component arrangement.

3. Location Two: Between an Outdoor Dry Cooler and an Indoor Facility Loop

A second plate heat exchanger may be installed on the facility side when the outdoor heat rejection circuit needs to be separated from the internal water network.

This exchanger is distinct from the plate heat exchanger inside the CDU.

3.1 Why an Outdoor Glycol Circuit May Need Separation

An outdoor dry cooler circuit may require glycol for freeze protection.

The indoor facility water circuit may use a different approved fluid.

An intermediate plate heat exchanger allows the two fluids to exchange heat without intentional mixing.

A simplified arrangement is:

Outdoor Dry Cooler/Glycol Loop ↔ Intermediate Plate Heat Exchanger ↔ Indoor FWS ↔ CDU ↔ TCS

The intermediate exchanger separates the outdoor and indoor facility circuits.

The CDU exchanger provides another boundary between the FWS and TCS.

3.2 Where Should the Intermediate Exchanger Be Located?

The heat exchanger should be located at the designed hydraulic boundary between the two loops.

It can be located in a machine room or designated mechanical area to provide access for piping, drainage, structural support, and maintenance.

Its exact location should minimize unnecessary piping and support the project's isolation and maintenance strategies.

There is no requirement that intermediate heat exchangers must be adjacent to dry coolers or atmospheric distillation units (CDUs).

3.3 Benefits and Tradeoffs

Separating the outdoor glycol circuit may reduce the volume of glycol required in the protected indoor network.

It can also allow different coolant treatment and operating pressure requirements on each side.

However, the extra heat exchanger introduces additional temperature approach and pressure losses.

The system must be evaluated to confirm that the benefits of isolation justify the additional equipment and operating requirements.

For related outdoor circuit design considerations, see How to Design Freeze Protection for a Dry Cooler System.

4. Location Three: Between Cooling Tower Water and a Closed Cooling Loop

A plate heat exchanger may also be used to separate cooling tower water from a closed facility cooling circuit.

4.1 Why an Open Cooling Tower Loop Needs Special Attention

Cooling tower water may be exposed to airborne contaminants and requires an appropriate water treatment program.

The water quality and maintenance requirements can differ from those of a closed facility cooling loop.

A plate heat exchanger creates a separation boundary between these circuits during normal operation.

4.2 Typical Installation Arrangement

A simplified arrangement may be:

Cooling Tower Circuit ↔ Plate Heat Exchanger ↔ Closed Facility Cooling Circuit

The location is selected according to the plant hydraulic design, service access, water treatment requirements, and heat exchanger performance.

This exchanger should not be confused with the CDU heat exchanger serving the IT coolant loop.

4.3 Cooling Tower Economizer Operation

Under suitable outdoor conditions, a well-designed water-side energy saver can provide cooling using cooling towers and heat exchangers without requiring the chiller compressor to operate at full load.

The required heat exchanger temperature differential, control valves, filtration system, and the operating condition of the cooling tower must be evaluated.

The presence of a plate heat exchanger alone does not guarantee natural cooling.

5. When an Additional Plate Heat Exchanger May Not Be Necessary

Adding more separation boundaries is not automatically beneficial.

Each exchanger requires installation space, piping, maintenance, and a sufficient temperature difference to transfer heat.

5.1 Avoid Unnecessary Temperature Penalties

If an existing CDU already provides the required FWS/TCS separation, another heat exchanger immediately upstream may not provide a meaningful benefit unless there is an additional hydraulic, fluid compatibility, or operating requirement.

The decision should be made at the system level.

5.2 Direct Facility Water Connections

Some engineered liquid cooling architectures connect facility water more directly to equipment.

These designs require explicit verification of water quality, allowable pressure, temperature, material compatibility, and IT equipment requirements.

A CDU is common, but it is not mandatory for every possible liquid cooling architecture.

5.3 Heat Recovery Applications

At the heat recovery boundary, a separate plate heat exchanger can be used to transfer heat from the facility cooling loop to another approved liquid system.

Its location depends on the heat source temperature, receiving system requirements, heat recovery load, and control method.

This arrangement should not be confused with the cooling interface of the main atmospheric unit (CDU).

6. How Installation Location Affects Temperature and Pressure Drop

The most important thermal consequence of heat exchanger placement is the temperature difference required across each separation boundary.

6.1 Understanding Approach Temperature

For a conventional CDU cooling arrangement, a cold-end approach temperature can be expressed as:

CDU Approach = TCS Supply Temperature − FWS Supply Temperature

The temperatures must be measured at the relevant heat exchanger ports.

A smaller approach at a specified heat duty generally requires greater heat-transfer capability and may affect the required exchanger size and hydraulic performance.

6.2 Illustrative Example: One Plate Heat Exchanger

Consider the following hypothetical operating conditions:

Parameter

Illustrative Value

TCS return temperature

40°C

TCS supply temperature

35°C

FWS supply temperature

30°C

FWS return temperature

35°C

CDU cold-end approach

5 K

The temperature approach is:

35°C − 30°C = 5 K

This temperature schedule is consistent with heat transferring from the warmer TCS coolant to the cooler FWS fluid.

The values are illustrative, not actual Aidear product performance data or recommended IT operating limits.

6.3 Adding an Intermediate Heat Exchanger

If an intermediate heat exchanger is installed between the outdoor cooling source and the FWS, the design must account for another temperature difference.

Due to the increased heat transfer boundary, the supply air temperature of the indoor facility may be higher than the supply air temperature of the outdoor loop.

A sufficient temperature difference is still required between the FWS and TCS airflow of the CDU.

Therefore, a complete temperature profile should be established from the IT equipment to the outdoor exhaust system.

6.4 Pressure Drop and Pumping Requirements

Each installed plate heat exchanger creates hydraulic resistance.

The designer must consider:

  • Pressure drop through the exchanger

  • Pipe and fitting losses

  • Filter and control valve losses

  • Pump operating range

  • Flow distribution

  • Minimum and maximum operating conditions

The total pressure losses must remain compatible with the circulation system.

A mechanically adequate exchanger pressure rating does not guarantee an acceptable pressure drop.

7. Installation Requirements Engineers Should Verify

7.1 Maintenance Clearance

Provide sufficient access for inspection, connections, isolation valves, and service activities.

Gasketed plate heat exchangers may require additional space for plate-pack opening or removal.

Brazed plate heat exchangers have different maintenance and replacement requirements.

The required clearance must be based on the specific exchanger model and manufacturer instructions.

7.2 Pipe Support and Mounting

Unsupported loads should not be applied to the piping system at heat exchanger connections.

Designers must consider piping weight, thermal expansion and contraction, vibration, and applicable connection load limits.

Heat exchangers should be installed according to the certified installation method for the selected model.

7.3 Isolation, Venting, and Drainage

The arrangement should allow the heat exchanger to be isolated and serviced safely.

Depending on the design, this may require isolation valves, drainage points, vents, and pressure protection.

The correct configuration must follow the manufacturer's installation instructions and the project P&ID.

7.4 Sensors and Performance Monitoring

Temperature and pressure measurement points should be positioned so that the exchanger's actual inlet and outlet conditions can be evaluated.

Flow measurements and differential pressure monitoring may also be required.

7.4.1 Commissioning Verification

Before handover, verify the correct flow direction, coolant properties, system cleanliness, operating flow rates, temperature conditions, and required alarms.

Final Installation Check: Confirm the Design Conditions

The engineering team should confirm that the installed configuration matches the approved P&ID and that the heat exchanger meets the specified operating requirements.

Testing and acceptance criteria should be agreed upon before commissioning.

8. Gasketed or Brazed Plate Heat Exchanger: Does Location Affect the Choice?

gasket plate heat exchanger (12).jpg

Installation location can influence the preferred exchanger construction, but it should not be used as the only selection criterion.

Selection Consideration

Gasketed Plate Heat Exchanger

Brazed Plate Heat Exchanger

Maintenance

Plate pack can generally be opened for suitable designs

Typically not mechanically opened for plate-by-plate cleaning

Installation space

Requires room for frame and servicing

Often compact

Sealing materials

Requires gasket compatibility review

Requires brazing material compatibility review

Cleaning strategy

Mechanical access may be possible

Typically relies on approved chemical cleaning or replacement

Configuration flexibility

Some designs allow plate-pack changes

Fixed construction

Typical selection factors

Service access, fouling, maintainability

Compact integration, compatible fluids, replacement strategy

Neither design is automatically superior for data center cooling.

For CDU installations, compactness and coolant compatibility may be important.

For larger facility-side systems, serviceability and fouling risk may influence the choice.

The final selection must consider thermal duty, pressure drop, fluid chemistry, available space, and equipment-specific technical requirements.

9. Plate Heat Exchanger Location Selection Checklist

Before selecting a heat exchanger position, answer the following questions.

Design Question

Information Required

What is being separated?

FWS/TCS, outdoor glycol/indoor FWS, cooling tower/closed loop, or another interface

What is the heat load?

Normal, minimum, and peak kW

What fluids are used?

Exact coolant type, concentration, and material compatibility

What are the temperature conditions?

Inlet and outlet temperatures on both sides

What flow rates are required?

Normal, minimum, and maximum flow

What pressure conditions apply?

Operating, design, differential pressure, and allowable pressure drop

Where will it be mounted?

CDU enclosure, rack area, plant room, or another designated location

How will it be maintained?

Isolation, cleaning, drainage, access, and replacement requirements

What equipment is nearby?

Pumps, valves, filters, CDU, dry cooler, or chiller

What reliability is required?

Redundancy, monitoring, failure response, and maintenance isolation

What must be verified?

Thermal performance, approved drawings, inspection, and commissioning

Buyers should request a project-specific heat exchanger selection and an approved hydraulic schematic rather than choosing a location from a generic product diagram.

10. Frequently Asked Questions

10.1 Is a Plate Heat Exchanger Always Installed Inside a CDU?

No.

Many liquid-to-liquid CDUs integrate a plate heat exchanger, but additional plate heat exchangers can be located in the facility cooling plant or at other separation boundaries.

10.2 Should a Plate Heat Exchanger Be Installed Before or After the CDU?

The question depends on the intended function.

The primary FWS/TCS heat exchanger is normally part of the CDU's thermal interface.

An additional facility-side exchanger may be upstream of the CDU within the overall cooling supply arrangement, but its position must follow the specific hydraulic design.

10.3 Can One Plate Heat Exchanger Separate All Data Center Cooling Loops?

Not necessarily.

A data center may require multiple separation boundaries with different fluids, temperatures, pressures, or operating responsibilities.

Each boundary must be evaluated individually.

10.4 Does Installing an Additional Heat Exchanger Improve Reliability?

It can provide useful fluid or hydraulic separation, but it also introduces more components, pressure losses, and potential failure points.

Reliability benefits depend on the complete architecture and maintenance strategy.

10.5 What Is the Most Important Document Before Installation?

An approved P&ID is essential because it identifies the actual connections, flow paths, valves, pumps, instrumentation, and separation boundaries.

It should be supported by a heat exchanger selection report and installation instructions.

11. Conclusion: Install the Heat Exchanger at the Required Separation Boundary

The correct installation location for a plate heat exchanger depends on which cooling loops need to exchange heat without sharing fluids.

In many direct-chip cooling systems, the plate heat exchanger is installed within the atmospheric unit (CDU), between the facility water system and the technical cooling system.

Additional plate heat exchangers can also be used to isolate outdoor glycol loops, cooling tower water, or other facility-side cooling networks.

Selection must consider temperature difference, pressure drop, fluid compatibility, maintenance space, control, and reliability requirements.

For engineers and procurement teams, the most efficient approach is to first define the cooling architecture, determine the required isolation boundaries, and then select the appropriate heat exchanger based on actual operating conditions.

Request a Plate Heat Exchanger Quote from Aidear

Aidear offers plate heat exchanger product categories that can be evaluated for suitable liquid-to-liquid heat-transfer applications.

For a data center cooling project, provide the intended installation position, fluids on both sides, required heat load, inlet and outlet temperatures, flow rates, pressure limits, mechanical constraints, and applicable technical requirements.

Specific compatibility, performance, and project acceptance requirements must be confirmed during equipment selection.

For more detailed purchasing requirements, see Aidear's CDU Heat Exchanger Selection Guide.

Request a Custom Quote to discuss your plate heat exchanger requirements.

Contact us

Can't Find Ideal Refrigeration System Solutions For Your Industries?

We are an excellent, specialized refrigeration system solutions provider for almost 20 years, our main products are various specifications of heat exchanges, air cooler, condenser and units, which are all covering a wide area of application.
Phone
 
+8613915061591
Address
 
Wujin High and New Technology Development Industry, Changzhou, Jiangsu,China

Products

Services

About Us

Links

© COPYRIGHT 2025 CHANGZHOU AIDEAR REFRIGERATION TECHNOLOGY CO., LTD. ALL RIGHTS RESERVED.