As AI servers, high-performance computing (HPC), and other high-density IT equipment generate increasing amounts of heat, liquid cooling has become an important part of modern data center thermal management.
However, supplying facility cooling water directly to sensitive server components is not always an appropriate solution.
Many direct-to-chip liquid cooling systems use two separate circuits: the Facility Water System (FWS) and the Technology Cooling System (TCS). These circuits exchange heat through a liquid-to-liquid heat exchanger, commonly integrated into a Coolant Distribution Unit (CDU).
This arrangement allows facility infrastructure and IT equipment to operate with different coolant quality requirements, temperature conditions, pressure levels, and flow rates.
Understanding why these loops are separated helps engineers, system integrators, and industrial equipment buyers evaluate cooling system reliability and make better technical decisions.
The facility water system (FWS) is the building-side cooling loop that provides cooling capacity for liquid-cooled infrastructure.
Depending on the system architecture, the FWS can be connected to chillers, dry coolers, and cooling towers via associated equipment, distribution pumps, and heat recovery systems.
The FWS delivers coolant to the facility side of the ambient temperature condenser (CDU) and removes heat to the exhaust system.
Its operating conditions depend on the cooling unit, outdoor conditions, equipment selection, and hydraulic design.
The FWS is not necessarily in the same loop as the chiller's condensate system.
The Technology Cooling System is the IT-facing liquid cooling circuit.
In a typical direct-to-chip arrangement, it circulates coolant between the CDU and IT equipment through components such as:
Server cold plates
Rack and row manifolds
Supply and return piping
Flexible hoses and quick-disconnect couplings
Valves, sensors, and filtration equipment
Cold plates absorb heat from processors, accelerators, and other components. Heated coolant returns to the CDU to transfer its heat to the facility-side circuit.
The TCS must satisfy coolant cleanliness and material compatibility requirements specified for the IT hardware.
The heat rejection path in a conventional liquid-to-liquid CDU arrangement is:
IT Components → Cold Plates → TCS Return → CDU Heat Exchanger → FWS Return → Facility Heat Rejection System
The cooling supply path runs in the opposite direction, from the facility cooling system through the CDU to the IT equipment.
The heat exchanger provides a thermal connection between the circuits while maintaining fluid separation during normal operation.
Facility cooling systems may contain dissolved minerals, corrosion products, suspended particles, deposits, or treatment chemicals.
These constituents may be adequately controlled for facility piping but unsuitable for sensitive IT cooling components.
Cold plates can contain small internal passages that are vulnerable to blockage or fouling.
Potential problems include:
Restricted coolant flow
Increased pressure drop
Reduced heat transfer
Localized overheating
Corrosion and material degradation
More frequent maintenance
Separating the TCS allows coolant chemistry and filtration to be managed according to IT equipment requirements rather than assuming that facility water is suitable.
FWS and TCS may require different coolants.
Outdoor facility loops may use a water-glycol mixture containing inhibitors for antifreeze. IT loops may require a different approved coolant that is compatible with the materials of the cold plates, seals, connectors, and other contact media.
These coolants should not be considered interchangeable.
Liquid-liquid heat exchangers allow different compatible coolants to operate on both sides without intentional mixing.
Piping networks in large facilities are susceptible to pressure variations due to factors such as pump operation, altitude, valve control, and hydraulic transients.
IT equipment must operate within its own pressure limits.
Hydraulically decoupled ambient temperature distribution units (CDUs) can operate independently of the facility's distribution pump management thermal control system (TCS) for circulation and pressure control.
However, decoupling does not eliminate pressure-related risks. The CDU heat exchanger must be able to withstand the applicable design pressure and differential pressure, while the TCS still requires appropriate expansion, pressure control, and overpressure protection.
The temperature supplied by the facility cooling system may differ from the temperature required by IT equipment.
A suitably designed CDU can regulate TCS supply temperature through heat exchange, control valves, bypass arrangements, pumping, and monitoring.
The design must consider:
Maximum and minimum allowable IT coolant inlet temperatures
Changes in IT heat load
Facility water supply temperature variations
Coolant flow requirements
Heat exchanger temperature approach
Condensation risk
The CDU cannot provide a guaranteed TCS supply temperature unless sufficient facility cooling capacity and appropriate controls are available.
Condensation can occur when the temperature of exposed cooled surfaces is below the dew point temperature of the surrounding air.
A condensate distribution unit (CDU) helps maintain the IT coolant temperature above applicable condensation control thresholds.
This requires appropriate temperature and humidity measurements, control logic, and operating limits.
Loop isolation aids in condensation management but cannot replace proper control, insulation, or commissioning.
Facility cooling infrastructure and IT cooling equipment may be maintained by different teams.
Cooling Data Units (CDUs) establish a clear technical interface between these systems.
Facility personnel can manage the operation of cooling units and facility water treatment, while IT cooling specialists are responsible for managing TCS coolant quality, rack connections, and equipment requirements.
Clearly defining the responsibility for both loops is crucial, especially during commissioning, equipment replacement, maintenance, and incident response.
Design Factor | Facility Water System (FWS) | Technology Cooling System (TCS) |
|---|---|---|
Primary function | Supplies cooling capacity and carries heat to facility infrastructure | Removes heat from liquid-cooled IT components |
Main equipment | Facility pumps, piping, chillers, and heat rejection equipment | Cold plates, manifolds, hoses, and rack connections |
Coolant requirements | Based on facility equipment and treatment specifications | Based on IT hardware and wetted-material requirements |
Pressure conditions | Determined by facility hydraulic design | Determined by IT equipment and TCS operating limits |
Temperature control | Managed through the facility cooling plant | Managed to meet IT inlet requirements |
Filtration | Protects facility piping and heat exchangers | Protects narrow passages in IT cooling components |
Maintenance | Commonly facility operations | Commonly IT or specialist liquid cooling operations |
These are typical distinctions, not universal rules. Actual responsibilities and configurations depend on the project.
CDU heat exchangers allow the higher-temperature TCS coolant to transfer heat to the lower-temperature FWS fluid through separate heat exchange surfaces.
During normal operation, the two fluids remain in independent channels.
This accommodates different coolant chemistry and hydraulic conditions.
However, no heat exchanger can completely guarantee against internal leaks. Corrosion, mechanical damage, gasket failure, or manufacturing defects can all compromise the separation boundary.
For applications with stringent cross-contamination limits, appropriate design, inspection, monitoring, and fault response measures are required.
Plate heat exchangers are commonly used for liquid-liquid cooling due to their compact heat exchange area.
Depending on the application, ambient temperature cooling units (CDUs) can employ gasketed plate heat exchangers, brazed plate heat exchangers, or other suitable heat exchanger designs.
The correct selection depends on fluid compatibility, heat load, pressure rating, ease of maintenance, leakage requirements, and pressure drop.
Heat exchangers must transfer the specified heat load without exceeding the allowable pressure drop in any loop.
The nominal heat transfer coefficient of a product alone is insufficient for equipment selection.
Flow conditions, fluid properties, operating temperature, and heat exchanger geometry must also be considered.
All components in contact with the medium must be compatible with the fluid on their respective sides.
For gasketed plate heat exchangers, maintenance access may be required for inspection, cleaning, and gasket replacement.
The usage and maintenance characteristics of brazed plate heat exchangers differ.
No single structure should be described as universally superior to others without considering the specific circumstances of the project.
Before selecting a heat exchanger, confirm:
Fluid composition on both sides
Design and operating temperatures
Operating and differential pressures
Required heat-transfer capacity
Flow rates and allowable pressure drops
Heat exchanger approach temperature
Wetted-material compatibility
Inspection, testing, and maintenance requirements
For more detailed procurement information, refer to Aidear's CDU Heat Exchanger Selection Guide.
For a common cooling arrangement, the cold-end approach temperature can be expressed as:
Approach Temperature = TCS Supply Temperature − FWS Supply Temperature
This relationship describes the temperature difference between the two supply water streams at the heat exchanger under specific conditions.
A smaller temperature difference typically means a greater heat transfer capacity is required for a given load and will affect the size, structure, and pressure drop of the heat exchanger.
The supply water temperature of a TCS depends on the facility water temperature, coolant flow rate, heat load, heat exchanger performance, and control operating conditions.
Separating the cooling system (TCS) reduces the likelihood of sensitive IT components coming into contact with facility water and particulate matter.
However, contaminants can still enter the IT cooling loop during commissioning, maintenance, equipment additions, or component aging.
Facility-side filtration helps protect the heat exchanger against fouling.
TCS filtration helps protect cold plates and other narrow flow passages.
Filter selection should reflect the equipment requirements, fluid properties, allowable pressure drop, and maintenance strategy.
An increasing filter differential pressure may indicate particulate accumulation.
The maintenance plan should define inspection and replacement criteria while ensuring sufficient coolant flow remains available.
An independent circulation system enables the TCS to operate under hydraulic conditions suitable for IT equipment.
Changes in facility-side pumping do not necessarily result in a corresponding change in TCS flow rate.
However, disturbances in facility temperature and flow rate will still reduce available cooling capacity.
Hydraulic separation does not achieve complete operational independence.
Separate circuits can help engineers identify whether a problem originates in the facility plant, CDU, or TCS.
This is useful when investigating poor coolant quality, unexpected temperature changes, pressure losses, heat exchanger fouling, or leakage.
Isolation valves, measurement points, alarms, and documented procedures remain necessary.
High-availability data centers may require redundant cold power distribution units (CDUs), pumps, power supplies, power distribution paths, or cooling equipment.
Using independent loops can support modular system designs, but it does not automatically achieve N+1 or 2N redundancy.
Redundancy must be validated through assessments of real-world failure scenarios.
A dry cooler rejects heat from a circulating liquid to ambient air.
In a data center liquid cooling arrangement, it may form part of the facility-side heat rejection system.
A possible heat rejection path is:
IT Equipment → TCS → CDU → FWS → Dry Cooler
The actual piping arrangement may differ. Some facilities include additional heat exchangers, chillers, cooling towers, or glycol circuits.
A dry cooler is not a direct replacement for a CDU because the two devices perform different functions.
Dry cooler performance depends on ambient air temperature, airflow, entering fluid temperature, fluid flow, and equipment design.
During hot weather, the dry cooler may be unable to maintain the facility supply temperature required by the CDU without supplemental cooling.
The design must therefore be evaluated under the specified outdoor design conditions.
For relevant heat rejection equipment, see Aidear's Dry Cooler Product Category.
Intermediate heat exchangers can be useful when outdoor glycol loops and indoor facility loops require different fluids or operating conditions.
However, each additional heat exchanger introduces a temperature difference and hydraulic resistance.
The advantages of fluid separation should be evaluated along with thermal performance, pumping requirements, maintenance, and cost.
Consider a hypothetical direct-to-chip cooling system using a liquid-to-liquid CDU.
Parameter | Illustrative Value |
|---|---|
FWS entering the CDU | 28°C |
FWS leaving the CDU | 33°C |
TCS returning from IT equipment | 38°C |
TCS supplied to IT equipment | 33°C |
TCS temperature difference | 5 K |
Cold-end approach temperature | 5 K |
The cold-end approach is:
33°C − 28°C = 5 K
Although the FWS enters at 28°C, the IT equipment receives coolant at 33°C.
These temperatures illustrate the heat exchanger's operating principle and are not recommended design limits.
The example shows that FWS supply temperature and TCS supply temperature are not necessarily identical.
The heat exchanger requires an appropriate temperature difference to transfer heat.
Both circuits must satisfy their respective thermal and hydraulic operating requirements.
For single-phase liquid cooling, the sensible heat-transfer rate can be calculated using:
Q = ṁ × Cp × ΔT
Where:
Q = Heat-transfer rate (kW)
ṁ = Mass flow rate (kg/s)
Cp = Specific heat capacity (kJ/kg·K)
ΔT = Fluid temperature difference (K)
A complete selection also requires the appropriate fluid properties, flow rates, pressure losses, and operating range.
Illustrative Example: All numerical values in this section are hypothetical. They are not Aidear product specifications, test data, or performance guarantees.
Some liquid-cooled data centers use architectures that connect facility cooling water more directly to IT equipment.
These systems require careful coordination among the facility designer, IT manufacturer, and cooling equipment supplier.
According to the design scheme, direct connection can reduce the number of heat exchangers, shrink the installation footprint, and lower some equipment requirements.
Eliminating intermediate heat exchangers can also reduce the temperature difference associated with those exchangers.
These advantages depend on the specific application.
Without a conventional CDU separation boundary, engineers must address:
Facility water quality and filtration
IT wetted-material compatibility
Operating and transient pressures
Condensation prevention
Temperature and flow control
Leakage detection and response
Maintenance responsibilities
The functions normally provided by the CDU must be addressed elsewhere in the system.
Separate loops may be especially valuable when the facility network cannot consistently meet the IT equipment's water quality, pressure, temperature, or maintenance requirements.
The decision should consider lifecycle operation, reliability objectives, thermal performance, and the overall cooling architecture.
Requirement | Information to Confirm |
|---|---|
Cooling capacity | Normal, peak, and future thermal loads |
Supply and return temperatures | Normal and design operating conditions |
Flow rate | Available range and control strategy |
Coolant composition | Water treatment and glycol requirements |
Pressure conditions | Operating, design, and transient pressures |
Cooling infrastructure | Chiller, dry cooler, tower, or other arrangement |
Reliability | Redundancy and failure-response requirements |
Requirement | Information to Confirm |
|---|---|
IT heat load | Heat transferred into the liquid circuit |
Coolant inlet temperature | Approved IT equipment operating range |
Flow requirements | Rack and component flow conditions |
Pressure limits | IT equipment and TCS restrictions |
Coolant chemistry | Approved composition and materials |
Filtration | Particle control requirements |
Condensation management | Dew-point monitoring and controls |
Connections | Manifolds, hoses, and quick disconnects |
Before requesting a quotation, confirm:
Required heat-transfer capacity and operating range
Supply and return temperatures on both sides
Fluid composition and flow rates
Maximum allowable pressure drop
Design pressure and temperature
Heat exchanger materials
Required approach temperature
Filtration and maintenance expectations
Controls, alarms, and monitoring requirements
Inspection and testing specifications
The requirements should be documented and verified with the appropriate equipment suppliers.
Some engineered systems can, but the facility water must satisfy IT equipment requirements for cleanliness, chemistry, materials, pressure, and temperature.
A CDU makes it possible to manage these requirements separately.
In many CDU arrangements, the FWS is called the primary side and the TCS the secondary side.
However, primary and secondary may have different meanings elsewhere in a cooling plant. FWS and TCS are more precise terms for this interface.
Not necessarily. Many liquid-to-liquid CDUs use plate heat exchangers, but equipment architecture and heat exchanger construction vary.
No, not as a direct functional substitute.
A dry cooler rejects heat to ambient air. A conventional liquid-to-liquid CDU transfers heat between facility and IT circuits while managing TCS operating conditions.
No.
A separate cooling loop does not guarantee against external leaks or internal heat exchanger failure.
Suitable materials, pressure controls, leakage monitoring, maintenance, and failure-response procedures remain necessary.
Separating the Facility Water System from the Technology Cooling System is a common strategy in liquid-cooled data centers.
It allows facility cooling infrastructure and IT equipment to operate with different coolant chemistry, filtration, temperature, and pressure requirements.
The CDU heat exchanger provides the thermal connection while maintaining fluid separation under normal conditions.
This arrangement can support better coolant quality management, hydraulic control, and clearly defined maintenance responsibilities.
However, reliable operation depends on the complete system design—not simply the presence of a heat exchanger.
For engineers and buyers, clearly defining the boundaries between the FWS, CDU, and TCS is essential before selecting cooling equipment.
Aidear offers heat exchanger and dry cooler product categories relevant to industrial and facility-side cooling applications.
If your project requires a liquid-to-liquid heat exchanger or facility-side heat rejection equipment, provide the operating fluids, thermal duty, inlet and outlet temperatures, flow rates, pressure requirements, and applicable technical specifications.
These details can support an initial discussion of suitable equipment configurations and any additional engineering information required.
Request a Custom Quote to discuss your data center cooling project with Aidear.
Why Data Center Cooling Systems Use Separate Facility and IT Water Loops
What Causes Thermal Stress in Shell-and-Tube Heat Exchangers?
Microchannel vs Fin-Tube Heat Exchangers: Key Differences Explained
Microchannel vs Fin-and-Tube Coils: Which Is Better for an Outdoor Condenser?
Dry Cooler Performance Verification: What Should Industrial Buyers Request Before Ordering?
How to Check Coolant Compatibility Before Selecting a Brazed Plate Heat Exchanger
Industrial Chiller Factory Acceptance Test: What Should Buyers Check Before Shipment?