Maelezo ya Bidhaa
Vigezo vya Kiufundi
| Mfano | Urefu wa Msingi | Urefu wa Msingi | Unene wa bomba la gorofa | Fin Pitch | Urefu wa Fin | Kipenyo cha Nje cha Mbalimbali |
| SC-1900 | 1274[mm] | 1358[mm] | 25.4[mm] | 1.1[mm] | 8[mm] | 38[mm] |
| 50.16[katika] | 53.46[katika] | 1[katika] | 23[FPI] | 0.31[katika] | 1.5[katika] |
| Mfano | Urefu wa bomba la gorofa | Idadi ya Mirija ya Gorofa | Mzunguko | Kiasi cha Ndani | Ingizo Ndani ya Kipenyo | Outlet Ndani ya Kipenyo |
| SC-1900 | 2[mm] | 133 | 85/48 | 9.22[L] | 22.2[mm] | 22.2[mm] |
| 0.08[katika] | 562.6[katika 3] | 7/8[katika] | 7/8[katika] |
Ufungaji wa Jopo la Upande
Vibadilishaji joto vya Alumini microchannel hupanua na mkataba kwa joto la juu, hivyo uvumilivu fulani lazima uruhusiwe kwa ajili ya ufungaji wa mabano na vipengele vingine.

Vigezo vya Utendaji
| Kasi ya Hewa | Utendaji wa Uhamishaji Joto [KW/Btu/h×1000] | ||||||||
| [m/s] | [ft/dakika] | R410A | R134a | ||||||
| △ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
△ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
||
| 1 | 197 | 17.88/61.02 | 27.51/93.89 | 37.6/128.33 | 47.57/162.35 | 17.51/59.76 | 26.74/91.26 | 35.94/122.66 | 45.05/153.75 |
| 1.5 | 295 | 25.34/86.48 | 39.1/133.45 | 54.12/184.71 | 68.52/233.86 | 24.71/84.33 | 37.89/129.32 | 51.02/174.13 | 65.29/222.83 |
| 2 | 394 | 32.02/109.28 | 51/174.06 | 69.32/236.59 | 87.84/299.8 | 31.08/106.08 | 47.91/163.52 | 66.08/225.53 | 83.43/284.74 |
| 2.5 | 492 | 38.08/129.97 | 61.35/209.39 | 83.45/284.81 | 105.85/361.2 | 36.89/125.9 | 57/194.54 | 79.29/270.61 | 99.92/341.02 |
| 3 | 591 | 43.63/148.91 | 70.98/242.25 | 96.64/329.83 | 122.69/418.7 | 42.23/144.13 | 65.32/222.94 | 91.49/312.25 | 115.27/393.4 |
| Kasi ya Hewa | Utendaji wa Uhamishaji Joto [KW/Btu/h×1000] | ||||||||
| [m/s] | [ft/dakika] | R404A | R407C | ||||||
| △ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
△ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
||
| 1 | 197 | 17.88/61.02 | 27.45/93.69 | 37.95/129.52 | 47.9/163.48 | 11.26/38.43 | 22.38/76.38 | 32.18/109.83 | 41.91/143.04 |
| 1.5 | 295 | 25.06/85.53 | 40.17/137.1 | 54.41/185.7 | 68.87/235.05 | 16.69/56.96 | 31.64/107.99 | 45.69/155.94 | 60.83/207.61 |
| 2 | 394 | 31.4/107.17 | 51.3/175.09 | 69.61/237.58 | 88.15/300.85 | 20.84/71.13 | 39.98/136.45 | 59.4/202.73 | 77.85/265.7 |
| 2.5 | 492 | 37.63/128.43 | 61.45/209.73 | 83.62/285.39 | 105.98/361.71 | 24.54/83.75 | 47.42/161.84 | 71.35/243.52 | 93.49/319.08 |
| 3 | 591 | 45.38/154.88 | 71.04/242.46 | 96.62/329.76 | 122.6/418.43 | 27.83/94.98 | 54.46/185.87 | 82.51/281.6 | 108.16/369.15 |
Kushuka kwa Shinikizo la Upande wa Hewa
| Kasi ya Hewa | Kushuka kwa Shinikizo | Kiasi cha Hewa | |||
| [m/s] | [ft/dakika] | [Pa] |
[inchi H 2O] | [m 3/ h] |
[cfm] |
| 1 | 197 | 18.8 |
0.08 | 5955.0 |
3502.9 |
| 1.5 | 295 | 29.7 |
0.12 | 8932.5 |
5254.4 |
| 2 | 394 | 46.1 |
0.19 | 11910 |
7005.9 |
| 2.5 | 492 | 59.8 |
0.24 | 14885 |
8755.9 |
| 3 | 591 | 74.2 |
0.30 | 17860 |
10505.9 |