Maelezo ya Bidhaa
Vigezo vya Kiufundi
| Mfano | Urefu wa Msingi | Urefu wa Msingi | Unene wa bomba la gorofa | Fin Pitch | Urefu wa Fin | Kipenyo cha Nje cha Mbalimbali |
| SC-2000 | 2000[mm] | 1058[mm] | 25.4[mm] | 1.1[mm] | 8[mm] | 38[mm] |
| 78.74[katika] | 41.65[katika] | 1[katika] | 23[FPI] | 0.31[katika] | 1.5[katika] |
| Mfano | Urefu wa bomba la gorofa | Idadi ya Mirija ya Gorofa | Mzunguko | Kiasi cha Ndani | Ingizo Ndani ya Kipenyo | Outlet Ndani ya Kipenyo |
| SC-2000 | 2[mm] | 103 | 69/34 | ≈10.3[L] | 25.4[mm] | 22.2[mm] |
| 0.08[katika] | ≈628.6[katika 3] | 1[katika] | 7/8[katika] |
Ufungaji wa jopo la upande
Wabadilishaji wa joto wa Aluminium microchannel itapanua na mkataba kwa joto la juu, hivyo aina fulani ya uvumilivu lazima iruhusiwe kwa ajili ya ufungaji wa mabano, nk.

Vigezo vya utendaji
| Kasi ya upepo | Utendaji wa uhamishaji joto [KW/Btu/h×1000] | ||||||||
| [m/s] | [ft/dakika] | R410A | R134a | ||||||
| △ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
△ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
||
| 1 | 197 | 22.7/77.47 | 34.95/119.28 | 46.97/160.31 | 59.06/201.57 | 21.93/74.85 | 33.25/113.48 | 44.75/152.73 | 56.3/192.15 |
| 1.5 | 295 | 32.7/111.6 | 50.21/171.37 | 67.52/230.44 | 85/290.1 | 30.91/105.49 | 47.03/160.51 | 64.07/218.67 | 80.39/274.37 |
| 2 | 394 | 41.98/143.28 | 64.14/218.91 | 86.37/294.78 | 108.94/371.81 | 38.82/132.49 | 60.4/206.14 | 81.29/277.44 | 101.57/346.66 |
| 2.5 | 492 | 50.4/172.01 | 77.03/262.9 | 103.81/354.3 | 131.04/447.24 | 45.91/156.69 | 71.91/245.43 | 96.11/328.02 | 120.76/412.15 |
| 3 | 591 | 58.23/198.74 | 88.87/303.31 | 120.06/409.76 | 151.56/517.27 | 52.31/178.53 | 82.41/281.26 | 109.83/374.85 | 138.18/471.6 |
| Kasi ya upepo | Utendaji wa uhamishaji joto [KW/Btu/h×1000] | ||||||||
| [m/s] | [ft/dakika] | R404A | R407C | ||||||
| △ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
△ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
||
| 1 | 197 | 22.53/76.89 | 35.14/119.93 | 47.15/160.92 | 59.26/202.25 | 15.26/52.08 | 28.07/95.8 | 40.58/138.5 | 52.71/179.9 |
| 1.5 | 295 | 32.86/112.15 | 50.19/171.3 | 67.5/230.38 | 85/290.1 | 21.34/72.83 | 39.8/135.84 | 58.2/198.63 | 75.49/257.65 |
| 2 | 394 | 41.77/142.56 | 63.85/217.92 | 85.96/293.38 | 108.35/369.8 | 26.63/90.89 | 51.57/176.01 | 74.25/253.41 | 96.26/328.53 |
| 2.5 | 492 | 49.99/170.61 | 76.38/260.68 | 102.87/351.09 | 129.7/442.66 | 31.32/106.89 | 61.75/210.75 | 88.6/302.39 | 115.34/393.65 |
| 3 | 591 | 57.26/195.43 | 87.9/300 | 118.38/404.03 | 149.25/509.39 | 35.37/120.72 | 71.13/242.76 | 102/348.12 | 132.76/453.11 |
Data ya kushuka kwa shinikizo la upande wa hewa
| Kasi ya hewa | Kushuka kwa shinikizo | Kiasi cha hewa | |||
| [m/s] | [ft/dakika] | [Pa] |
[inchi H 2O] | [m 3/ h] |
[cfm] |
| 1 | 197 | 18.7 |
0.08 | 7330 |
4311.8 |
| 1.5 | 295 | 29.7 |
0.12 | 10995 |
6467.5 |
| 2 | 394 | 46 |
0.18 | 14660 |
8623.5 |
| 2.5 | 492 | 59.7 |
0.24 | 18330 |
10782.4 |
| 3 | 591 | 74 |
0.3 | 21995 |
12938.2 |