Productbeschrijving
Technische parameters
| Model | Kernlengte | Kern Hoogte | Dikte platte buis | Finse toonhoogte | Vinhoogte | Buitendiameter verdeelstuk |
| SC-1700 | 1324 [mm] | 638[mm] | 25,4[mm] | 1,1 [mm] | 8 [mm] | 38 [mm] |
| 52,13[in] | 25.12[in] | 1[in] | 23[FPI] | 0,31[in] | 1,5[in] |
| Model | Hoogte platte buis | Aantal platte buizen | Circuit | Intern volume | Inlaat binnendiameter | Uitlaat binnendiameter |
| SC-1700 | 2[mm] | 61 | 43/18 | ≈4,35[L] | 15,88 [mm] | 12,7 [mm] |
| 0,08[in] | ≈265,46[inch 3] | 5/8[in] | 1/2[in] |
Installatie op zijpanelen
Aluminium warmtewisselaars met microkanalen zetten uit en krimpen bij hoge temperaturen, dus er moeten bepaalde toleranties worden toegestaan voor montage van beugels en andere aspecten.

Prestatieparameters
| Luchtsnelheid | Warmteoverdrachtsprestaties [KW/Btu/h×1000] | ||||||||
| [mevrouw] | [ft/min] | R410A | R134a | ||||||
| △ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
△ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
||
| 1 | 197 | 8.51/29.04 | 13.08/44.64 | 18.03/61.54 | 22,78/77,75 | 8.39/28.63 | 12,84/43,82 | 17.21/58.74 | 21.79/74.37 |
| 1.5 | 295 | 12.08/41.23 | 19.11/65.22 | 25,89/88,36 | 32,84/112,08 | 11.78/40.20 | 18.09/61.74 | 24.91/85.02 | 31,32/106,89 |
| 2 | 394 | 15.32/52.29 | 24.48/83.55 | 33.21/113.34 | 42,08/143,62 | 14,89/50,82 | 22.88/78.09 | 31,74/108,33 | 39,99/136,48 |
| 2.5 | 492 | 18,91/64,54 | 29,41/100,38 | 40,03/136,6 | 50,66/172,90 | 17,72/60,48 | 28.03/95.67 | 38.09/130.00 | 48,12/164,23 |
| 3 | 591 | 21,68/73,99 | 34.12/116.45 | 46.32/158.09 | 58,84/200,82 | 20.21/68.98 | 32,29/110,20 | 43,91/149,86 | 55,26/188,60 |
| Luchtsnelheid | Warmteoverdrachtsprestaties [KW/Btu/h×1000] | ||||||||
| [mevrouw] | [ft/min] | R404A | R407C | ||||||
| △ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
△ =10K △ =18°F |
△ =15K △ =27°F |
△ =2K △ =36°F |
△ =25K △ =45°F |
||
| 1 | 197 | 8,45/28,84 | 13.38/45.67 | 18.62/63.55 | 22,95/78,33 | 5.42/18.50 | 10.68/36.45 | 15.42/52.63 | 20.31/69.32 |
| 1.5 | 295 | 12.12/41.37 | 19.28/65.80 | 26.11/89.11 | 33.04/112.76 | 7.94/27.10 | 15.09/51.50 | 22.31/76.14 | 29,21/99,69 |
| 2 | 394 | 15,78/53,86 | 24.62/84.03 | 33.42/114.06 | 42,19/143,99 | 9,92/33,86 | 19.07/65.09 | 28,54/97,41 | 37,33/127,41 |
| 2.5 | 492 | 18,89/64,47 | 29,52/100,75 | 40,11/136,89 | 50,75/173,21 | 11,68/39,86 | 23.49/80.17 | 34,21/116,76 | 44,78/152,83 |
| 3 | 591 | 21.82/74.47 | 34.02/116.14 | 46,42/158,43 | 58,82/200,75 | 13.15/44.88 | 27.06/92.35 | 39,62/135,22 | 51,89/177,10 |
Drukval aan de luchtzijde
| Luchtsnelheid | Drukdaling | Luchtvolume | |||
| [mevrouw] | [ft/min] | [Pa] |
[inch HO 2] | [m 3/u] |
[cfm] |
| 1 | 197 | 18.6 |
0.07 | 2860.0 |
1682.4 |
| 1.5 | 295 | 29.5 |
0.12 | 4285.0 |
2520.6 |
| 2 | 394 | 45.8 |
0.18 | 5715.0 |
3361.8 |
| 2.5 | 492 | 59.4 |
0.24 | 7145.0 |
4202.9 |
| 3 | 591 | 73.6 |
0.30 | 8570.0 |
5041.2 |